Copley Controls Serial Encoder Guide de l'utilisateur Page 106

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 180
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 105
Quick Setup with CME 2 Xenus XTL User Guide
98 Copley Controls Corp.
5.7.2: PWM Input
For more information, see PWM Input (p. 17).
5.7.2.1 Click PWM Command to open the PWM Command screen.
5.7.2.2 Set the input options described below.
Option Description
Scaling Current mode: output current at 100% duty cycle.
Range: 0 to 10,000,000 A. Default: Peak Current value.
Velocity mode: output velocity at 100% duty cycle.
Range: 0 to 100,000 rpm (mm/sec).
Default: Maximum Velocity value.
PWM Input
Type
One wire 50% or two wire 100% with direction.
Options Invert PWM input: Inverts the PWM logic.
Allow 100% output: Overrides the 100% command safety measure.
See Failsafe Protection from 0 or 100% Duty Cycle Commands (p. 17).
Invert Sign Input: In 100% duty cycle mode, inverts the polarity of the directional input.
5.7.2.3 Click Close.
5.7.2.4 On the Main screen, click Save to Flash.
5.7.2.5 Proceed to Auto Phase (p. 102).
Vue de la page 105
1 2 ... 101 102 103 104 105 106 107 108 109 110 111 ... 179 180

Commentaires sur ces manuels

Pas de commentaire